Battery Maintenance

To ensure the integrity of any Uninterruptible Powerlead acid' (VRLA) batteries( often referred to as just
Supply, Telecommunications 48V system or'sealed lead acid batteries').
generator, the lead acid batteries must be checkedWet cell battery maintenance can be more time
and maintained.consuming, as the trade off against increased life
Surprisingly what ever the cost of your Powerexpectancy is the higher cost of maintenance due to
Protection system, whether it is a stand alone UPSthe necessity of taking specific gravity readings and
System or Standby Diesel Generators the most'topping' up the cell. A visual check of wet cell
common single point of failure are the batteries.batteries needs to be undertaken on a more regular
High resistance, leakage or open circuits will causebasis as any noticeable drop in electrolyte level must
batteries to fail; no longer providing the expectedbe swiftly rectified.
autonomy or, in the case of a generator the inabilityThe VRLA 'lead acid' battery is more difficult to
to start. The Result - loss of the site load. Thencheck being a sealed battery. The most common
suddenly you require a 24-7 emergency call outmethod of testing, often built into most UPS
engineer.systems equipment is a battery self test which is
Uninterruptible power supplies may have internaloften carried out automatically on a weekly/monthly
batteries or housed in separate battery cabinets.time cycle. If the test fails the UPS system will
Each battery has a recommended design life, usuallygenerate an alarm. The major drawback is if the
5 years or 10 years, although these are optimistic asequipment is supporting a small load comparative to
they don't take into account high usage of the UPSthe capacity of the equipment the battery will not be
Battery system caused by intermittent spikes, brownworked very hard and could prematurely fail.
outs or voltage fluctuations which are absorbed byThe more reliable means of regular testing a battery
the batteries to protect your mission critical sensitiveis either:-
systems.1. By loading the battery to one third of its capacity
Even though the battery may have an operating lifeand carrying out a capacity test
expectancy stated by the manufacturer of typically2. impedance testing -increasingly popular as it's
up to ten years, if it is not checked on a regular basisnon-intrusive.
it can and will fail. In a string of 32 blocs all it takes isThere are several methods of achieving the same
one battery to become high impedance and theresult but one method is to pass a known ac current
complete string will be useless as the load will bethrough the battery and measure the ac voltage and
unable to draw the current it requires and as a resultthus, by using Ohms Law calculate the battery
the load will be lost and your critical load will fall over.impedance. These results can be compared with the
The old batteries can be removed and new batteriesmanufacturer's recommended value and by keeping
supplied.records can be compared over a period of time
The most obvious signs of Battery leakage due toallowing a replacement programme to be
failure within the sealed lead acid battery causing theimplemented when the battery impedance has
casing to split can be visible. Other issues of highreached a preset value.
impedance and open circuit are not obvious andWhich ever method of battery testing you choose ,
require regular checks.regular battery maintenance is an integral part of any
There are a number of different types of batteryUninterruptible Power Supply or Generator standby
construction but they can be loosely divided into topower protection system .
two common types-'wet cells' and 'valve regulated